HR200 V




A ducted heat recovery unit for internal rooms. Self-contained and includes two mixed flow speed controllable fans. Using a high performance, polymeric heat exchange cube together with two power fans, the HR200V can boast a temperature efficiency of up to 70%. Low speed for trickle ventilation mode.

Specially designed to provide ventilation for small internal rooms in commercial, educational and leisure applications. Ventilation is achieved by using nominal 150mm diameter flexible ducting. The unit is completely self-contained and includes two mixed flow speed controllable fans plus a high efficiency polymeric heat exchanger.


HR200V is designed for mounting in a cupboard, a ceiling void or above a suspended ceiling. Four spigots are provided for simple connection to 150mm flexible ducting. When passing through an unheated area insulated ducting should be used.


HR200V to be used with a 150VA Transformer for maximum controllability

Motor Speed 1 2 3
Voltage 140 160 240
Watts 52 60 110
Volume l/s (FID)
Supply 48 56 70
Extract 67 79 103



Weight: 5.6kg


Sound Power Spectrum (Max Speed) 63Hz 125Hz 250Hz 500Hz 1KHz 2KHz 4KHz 8KHz dB(A) @ 3m
62 65 70 62 52 51 46 46 43

Power Consumption
Maximum 110.0W



 Typical Specifications

Supply and install a HR200V Wholehouse heat recovery unit as manufactured by:

Vent-Axia Clean Air Systems
Fleming Way
West Sussex
RH10 9YX 




Max ventilation rate (FID)







N° speed settings

Refer to type of control

Efficiency: The unit should retain up to 70% of the temperature differential of out going air.

Heat exchanger: should be of a multi plate cross-flow type constructed out of a polymeric plastic with ultra sonic welded joints.

Motor: should be a 240V 50Hz A/C with sleeve bearings, greased for life. It shall operate up to an ambient temperature of 40°C and be fitted with a manual reset thermal overload protective device.

Fan: The 2-N° polymeric fan impellers should be of a dynamically balanced mixed flow type.

Controls: The unit should be operated via either an Electronic Speed Controller or Trickle Boost Switch/Sensors via 150VA Transformer.

Ducting spigots: The unit should have 4-N° 150mm Ø x 50mm spigots. (Can be converted to flat ducting).

Filter: not fitted.

Condensation: the outlet provided should be 22mm Ø located on the underside of the unit.

Construction: The unit outer case should be a rigid ABS moulding. The external grille should be a cream coloured ABS moulding. The spigot plates should be black vacuum formed PVC.

Mains electrical supply: 230VAC 50Hz.

Complies to the following approvals/directives: CE.

There are no softwares available for download for this particular product.