HR500 DP Passive Heat Exchange Unit

Description

Overview

A 'stand alone' Heat Exchange Unit which will transfer up to 70% of the outgoing heat to incoming air. Polymeric construction with spigots to suit 200, 250 and 315mm Ø flexible ductwork. Module accessible for routine cleaning. Condensate outlet provided. Ideal for use in air conditioned environments. The heat exchanger works at the same high efficiency,automatically keeping a cool room cool.

Performance of the Heat Exchange Unit: At 180 l/s achieves 70% temperature efficiency (balanced airflow). Ideal for schools, pubs, offices and leisure industries.

 

 

Installation

HEU Installation

The HEU unit should be installed with a slope towards the drain fitting of approximately 3 degrees.

 

 

Fan Options

Fan Options
ACP ACM ACQ
ACP ACM ACQ

Performance

WARNING: Both airflows to be subjected to the same conditions. (ie. negative or positive pressure)

 



 



Dimensions

Weight: 10kg

 



Typical Specifications

Supply and install a HR500DP passive semi remote ducted heat recovery unit for installation on an internal wall as manufactured by:

Vent-Axia Clean Air Systems
Fleming Way
Crawley
West Sussex
RH10 9YX

Performance: m³/h l/s
Max ventilation rate 1000 278

Efficiency: The unit should retain up to 70% of the temperature differential of out going air.

Heat exchanger: Should be of a multi plate cross-flow type constructed out of a polymeric plastic with ultra sonic welded joints.

Fan: As a passive device the unit shall require 2-N° additional remote in-line fans.These should typically be Vent-Axia centrifugal type fans.

Ducting spigots: The unit should provide 315, 250 and 200 mm Ø spigots for duct connections. The unit cannot be handed.

Filter: Not fitted.

Condensation: The outlet provided should be 22mm Ø located on the lower side of the unit.

Construction: The unit outer case should be a rigid HIPs moulding configured so as to make the unit telescopic. The external grille and the spigot plate should be a cream coloured ABS moulding.

Sound Levels: As per specified in-line fan unit

Mains electrical supply: As per specified in-line fan unit

Power Consumption: As per specified in-line fan unit