HR500 EP

Description

Overview

The HR500EP unit is designed for mounting in an external wall. The unit has no fans fitted and is ideal for systems where centrifugal in-line fans are used to overcome increased external static pressure from long duct runs or multiple grille applications.The unit incorporates a polymer heat exchanger in a light weight plastic enclosure with two spigots for easy ducting connection.The unit maintains the separation of extracted air and fresh air supply whilst transferring up to 70% of the waste heat from extracted foul air.

Performance of HR500EP: Up to 244 l/s FID capacity (balanced airflow). Ideal for computer rooms, classrooms, offices and the health & leisure industries.

 

Installation

The HR500EP unit is designed for mounting in an external wall and should be fitted to provide a 3° slope to outside to provide condensate drainage.The unit has no fans fitted and is ideal for systems where centrifugal in-line fans are used to overcome increased external static pressure from long-duct runs or multiple-grille applications.

 

Fan Options

 

Fan Options
ACP ACM ACQ
ACP ACM ACQ

 

Performance

Graphs:

 



 



 

Dimensions

Fitting Hole Size: 610mm × 381mm
Weight: 10kg

 



 
 

Typical Specifications

Supply and install a HR500EP passive semi remote ducted heat recovery unit for installation on an external wall as manufactured by:

Vent-Axia Clean Air Systems
Fleming Way
Crawley
West Sussex
RH10 9YX

Performance: m³/h l/s
Max ventilation rate 880 244

Efficiency: The unit should retain up to 70% of the temperature differential of out going air.

Heat exchanger: Should be of a multi plate cross-flow type constructed out of a polymeric plastic with ultra sonic welded joints.

Fan: As a passive device the unit shall require 2No additional remote in-line fans.These should typically be Vent-Axia in-line centrifugal type fan.

Ducting spigots: The unit should provide 315, 250 and 200mm Ø spigots for both duct connections.The unit cannot be handed.

Filter: Should be a washable reticulated foam type coarse filter.

Condensation: The outlet provided should be 22mm Ø located on the lower side of the unit.

Construction: The unit outer case should be a rigid HIPs moulding configured so as to make the unit telescopic.The external grille and the spigot plate should be a cream coloured ABS moulding.

Sound Levels: As per specified in-line fan unit

Mains electrical supply: As per specified in-line fan unit

Power Consumption: As per specified in-line fan unit

There are no softwares available for download for this particular product.