I GENERAL
A.
Supply or exhaust registers shall be Lindab's SPIROcomfort®
model RGS-3 for direct mounting on spiral ducts of sizes shown on
the plans or outlet schedule.
B.
The register is to be mounted without the use of a rectangular register
tap. The top and bottom flanges are to meet flush with the spiral
duct wall regardless of duct diameter. End caps shall be provided
that conform to the varying duct diameter.
II
MATERIALS
A.
The register shall be manufactured of 20 or 22 gauge galvanized
steel without further surface treatment. Welds or other surface
discolorations on the register are unacceptable.
III
CONSTRUCTION
A.
The register shall have double deflection adjustable blades with
the front blades parallel to the short dimension of the register.
Blades shall be placed on ¾" centers and shall have
steel friction pivots on both ends to allow for individual blade
adjustment without loosening or rattling.
B.
Screw holes shall be countersunk for a flush, neat appearance.
IV
DAMPER
A.
The volume damper shall be of the single blade type manufactured
from 20 gauge electro-galvanized steel.
B.
Volume damper shall be operable from the face of the register via
a volume control rod. Notched rod shall be fixed in place by a tension
lock located at the front of the register.
V
PERFORMANCE
A. Performance of register shall be as per manufacturer's catalogued
data. Manufacturers whose registers utilize a rectangular register
tap to adapt to use with spiral duct shall submit correction factors
for their catalogued data.